What an EICR Is, and What the Codes Actually Mean

Electrical Installation Condition Reports are full of codes that decide whether you have a problem. Here is how to read one.

BeydilliBright Ltd. 3 min read
Three recessed metal back boxes chased into a plastered wall with cables terminated into lever connectors, ready for accessories

If you own, let or manage property, an Electrical Installation Condition Report will land on your desk sooner or later. They are dense documents, and the part that matters — whether you have an urgent problem or a list of suggestions — is buried in a column of codes.

What an EICR is

An EICR is a formal inspection and test of a fixed electrical installation: the wiring, the consumer unit, the accessories and the earthing arrangement. It does not cover appliances that plug in.

It produces two things: an overall assessment of satisfactory or unsatisfactory, and a schedule of observations, each with a code.

Importantly, an EICR is a snapshot of condition, not a certificate for new work. New work gets an Electrical Installation Certificate. The two are frequently confused, including by people asking for one and being given the other.

The codes

C1 — danger present

Risk of injury exists right now. Exposed live conductors, for example. A C1 requires immediate action, and a competent inspector will normally make the situation safe before leaving, or isolate the affected part.

C2 — potentially dangerous

The installation is not dangerous as it stands, but it would become so if a fault occurred. Missing earthing, absent RCD protection where it is required, that sort of thing. C2 items require urgent remedial action.

C3 — improvement recommended

Not dangerous, and not a requirement. C3 observations typically reflect that the installation was compliant when it was built and standards have moved on. You can address them, and often should when convenient, but a report with only C3 items is still satisfactory.

FI — further investigation required

Something could not be assessed during the inspection and needs investigating. FI items make a report unsatisfactory, because the inspector cannot confirm the installation is safe.

What makes a report unsatisfactory

Any C1, C2 or FI. C3 items alone do not. This is the single most useful thing to understand about an EICR, because it separates "you have a problem" from "here are some suggestions".

What to do with an unsatisfactory report

Address the C1, C2 and FI items. Once the remedial work is complete, that work is certified — and depending on its scope, the installation may warrant reinspection.

The practical advice is to work through the observations as one piece of work rather than one at a time. Several observations frequently share a root cause, and dealing with them together is usually quicker and cheaper than three separate visits.

We carry out remedial work arising from inspection reports regularly. Sending us the report is genuinely the most useful first step — it tells us what the job actually is.

A word on inconsistency

Coding involves judgement, and different inspectors occasionally code the same observation differently. A report that codes a great many things C2 when they look more like C3 is worth asking about — not because inspectors are dishonest, but because an inspection that leads directly to a quote for remedial work from the same party is a situation where questions are reasonable.

How often

General guidance: up to ten years for owner-occupied homes, up to five years or at each change of tenancy for rented domestic property, and typically five years for commercial premises, with shorter intervals in higher-risk environments.

These are maximum intervals rather than targets. An installation that has been altered repeatedly, or one where something has already gone wrong, warrants looking at sooner.