Emergency Lighting: Requirements and Testing

Emergency lighting is one of the most commonly neglected parts of a commercial installation — and one of the easiest to get right.

BeydilliBright Ltd. 3 min read
An open-plan ground floor during refurbishment, with a linear wall light, pendant fittings and a fabric shade lit for the first time beside a glazed internal door and staircase

Emergency lighting exists for one scenario: the normal lighting has failed and people need to leave the building safely. It is invisible until that moment, which is precisely why it gets neglected.

What it has to do

Emergency lighting must illuminate escape routes sufficiently for people to leave safely, and it must do so for a specified duration on its own power supply — commonly three hours.

It also needs to highlight the things people need to find: exit doors, changes of direction, stairs, fire-fighting equipment and first aid points.

Maintained and non-maintained

Non-maintained fittings are off in normal conditions and illuminate only on supply failure. Typical in offices and workplaces.

Maintained fittings are lit all the time and stay lit on failure. Used where the space may be occupied in darkness — cinemas, venues, some hospitality.

Illuminated exit signs are usually maintained, since a sign that is only visible during an emergency is less useful than one people have already noticed.

Self-contained and central battery

Most installations use self-contained fittings, each with its own battery. Simple, resilient — a fault affects one fitting — but each battery needs replacing eventually, and in a large building that is a lot of batteries.

Central battery systems power all fittings from one location. Maintenance is centralised, but a failure affects everything.

Testing

Two routine tests:

  • Monthly function test. Brief — simulate a supply failure and confirm every fitting illuminates.
  • Annual full-duration test. Run the system for its rated duration and confirm every fitting stays lit throughout.

The annual test is the one that finds degraded batteries, and it is the one most often skipped because it takes time. Schedule it when the building is empty — after a full discharge, the batteries need time to recharge before the system is protective again.

Results go in the logbook. The logbook is the evidence that the duty has been met.

The most common failure

Not equipment failure. It is layout change.

A building is reconfigured, walls move, escape routes change — and the emergency lighting still reflects the old plan. Fittings illuminate corridors that no longer exist while new escape routes have no coverage at all.

Any change to layout or use should trigger a review. This is the single most frequent emergency lighting gap we find.

Batteries

Emergency lighting batteries have a finite life, typically around four years. A fitting whose battery has degraded will pass a function test — it lights up — and fail a duration test within minutes.

That is exactly why the annual duration test exists, and exactly why skipping it is worse than it appears.

Getting it checked